Permit: T06EL02349

Parcel: 12611153A


Addresses:

4431 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02349

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MARKING LABEL TO BE PERMANENT METAL ADDRESS LABEL
2. USE APPROVED HANDLE TIE
3. BREAKER TO BE LISTED FOR USE BY MANUFACTURE
4. INTERIOR PANEL IS A 2 WIRE UNGROUNDED SYSTEM
5. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING.
12/11/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WATER HEATER NOT ALLOWED TO BE CORD & PLUG CONNECTED.
2. INTERIOR SUB-PANEL IS AN UNGROUNDED SYSTEM. WE HAVE GROUNDED RECEPTACLS CONNECTED. ONLY ONE NEUTRAL TO A LUG TERMINATION.
3. PLEASE UNLOCK EXTERIOR SUB-PANEL AND LABEL.
4. RECONNECT GROUND WIRE.