Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 12/13/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* COPPER WATER PIPE CANNOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR 250.122 CONDUCTOR TO BE AS PER 250.134 OR A GROUNDING ELECTRODE SYSTEM TO BE INSTALLED PER 250.50 |
|
| 12/12/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/11/2006 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* |