Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL02322
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/08/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING SYSTEM ELECTRODE CONDUCTOR HAS BEEN CUT. REGROUND SERVICE PER CODE. 2. REMOVE EXTENSION LOAD WIRE TIED BETWEEN SERVICES. 3. SUPPORT 3/4" CONDUIT BELOW PANEL. 4. INSTALL ROMEX CONNECTOR AT 45 BOX IN BACK ROOM. 5. INSTALL WORKING SMOKE DETECTORS IN SLEEPING AREAS. 6. INSTALL MISSING COVER PLATES FOR RECEPTS & SWITCHES 7. INSTALL BREAKER BLANK ON PANEL DEAD FRONT AT SERVICE. |