Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. GAS BOND CLAMP LOOSE
2. WHERE IS WATER BOND?
3. SECURE TO STRUCTURE OR BURY MINIMUM 12" GROUNDING ELECTRODE CONDUCTOR.
4. MOVE SERVICE LUGS TO OVERHEAD POSITION
5. PANEL DIRECTORY NOT MARKED CORRECTLY
6. WIRE OLD G.E.C INTO NEW PANEL (OLD GROUND).