Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. GAS BOND CLAMP LOOSE 2. WHERE IS WATER BOND? 3. SECURE TO STRUCTURE OR BURY MINIMUM 12" GROUNDING ELECTRODE CONDUCTOR. 4. MOVE SERVICE LUGS TO OVERHEAD POSITION 5. PANEL DIRECTORY NOT MARKED CORRECTLY 6. WIRE OLD G.E.C INTO NEW PANEL (OLD GROUND). |