Permit: T06EL02303

Parcel: 113020610


Addresses:

3850 N PARK AV #A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/16/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAIN WATER BOND CLAMP IS LOOSE AND HAS COMPRESSED COPPER WATER PIPE.
2. PROVIDE ACCESS TO UNITS FOR PANEL AND BONDING CONNECTIONS.
02/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOND MAST-NEC 250.92 AND NEC 250.102
2) BOND FOR GAS AND WATER UNDERSIZED-NEC 250.104 A1
3) IDENTIFY SERVICE DISCONNECTS, ADDRESS AND UNIT NUMBERS
4) INSTALL FLASHING FOR MAST
CHECK NEUTRALS/GROUND IN SUB-PANEL