Permit: T06EL02298

Parcel: 123151160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02298

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :$
1) THERE APPEARS TO BE NEW INTERIOR BRANCH CKT WIRING FOR THESE UNITS, HOWEVER CONTRACTOR HAS STATED HE HAS DONE SERVICE AND SUB PANEL ONLY. NO INTERIOR INSPECTION
05/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROPERLY IDENTIFY ALL PANEL DIRECTORY'S
2. PROVIDE LADDER AND INTERIOR ACCESS TO ALL UNITS

PARTIAL INSPECTION ONLY AT THIS TIME
04/04/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CALL WHEN SWITCHOVER IS COMPLETE
04/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. SERVICE DISCONNECTS TO BE IDENTIFIED AS "SERVICE DISCONNECT" NOT "MAIN DISCONNECT" - NEC 230.70B
2. EQUIPMENT GROUNDS NOT TO BE SHARED UNDER SAME TERMINATION AT SERVICE UNLESS LUG IS LISTED FOR THAT USE - NEC 110.3B
3. MAIN BONDING JUMPER (BAR) NOT INSTALLED IN SERVICE
NEC 110.3B, NEC 250.28
03/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B
2. NEED BUSHING FOR CONDUCTORS #4 AND LARGER -
NEC 300.4 F
3. REMOVE PAINT UNDER BOND CLAMPS, INSTALL NEW CLAMPS - DO NOT USE OLD ONES, TIGHTEN ALL SCREWS -
NEC 250.12, 110
4. NEED AN EQUIPMENT GROUNDING CONDUCTOR TO SUB-PANELS - NEC 250.142 B
5. IDENTIFY UNIT # ON EACH SUB-PANEL EXTERIOR

- MAKE SURE EACH STRUCTURE WATER/GAS BONDED
- NEUTRALS & GROUNDS FLOAT @ SUB-PANELS
- BOND & GROUNDING ELECTRODE CONDUCTORS WITH GROUNDS
- BOND TO ENCLOSURE AND NEUTRALS FLOAT -
SEE NEC 250.32