Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/30/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/29/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NM CABLE NOT ALLOWED FOR DIRECT BURIAL - WIRING METHOD TO BE AS PER 300.5 FOR DEPTHS - ALSO LOOSE FITTINGS. 2. SUPPORT NEW CONDUIT TO COOLER AND DISCONNECTS AS PER CODE. 3. BOND JUNCTION BOX ENCLOSURE 250.148 4. VERIFY FILL FOR SPLICES IN CONDUIT BODY. 5. SUB-PANEL IS A 2-WIRE UNGROUNDED SYSTEM - CORRECLTY IDENTIFY THE GROUNDED CONDUCTOR. |