Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/12/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* VERIFY GROUND RODS AS PER PREVIOUS INSPECTION |
|
| 12/11/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RISER SUPPORT ON ROOF MUST BE A LISTED TYPE, HOMEMADE OUT OF EMT FLATENED AT ENDS NOT APPROVED. 2. USE BOND BUSHING AT 1" EMT TERMINATIONS. WHEN USING CONCENTRIC KO'S, CODE REQUIRES BUSHINGS FOR #4 OR LARGER. 3. PROVIDE ENDS OF CUT OFF GROUND RODS TO VERIFY LENGTH CUT. IF NOT, DRIVE NEW RODS 8' INTO EARTH PER CODE. |