Permit: T06EL02293

Parcel: 121090290


Addresses:

5312 E PEACH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/13/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/12/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
VERIFY GROUND RODS AS PER PREVIOUS INSPECTION
12/11/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RISER SUPPORT ON ROOF MUST BE A LISTED TYPE, HOMEMADE OUT OF EMT FLATENED AT ENDS NOT APPROVED.
2. USE BOND BUSHING AT 1" EMT TERMINATIONS. WHEN USING CONCENTRIC KO'S, CODE REQUIRES BUSHINGS FOR #4 OR LARGER.
3. PROVIDE ENDS OF CUT OFF GROUND RODS TO VERIFY LENGTH CUT. IF NOT, DRIVE NEW RODS 8' INTO EARTH PER CODE.