Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK UNDERGROUND-360 DEGREE OF BENDS IN 1" PVC 2) OK GROUND RODS 3) OK GAS AND WATER BOND 4) RECALL AFTER TEP TIE IN |
|
| 08/10/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS TO BE MINIMUM 6' APART NEC 250.56 & 250.53 2) SCHEDULE 80 PVC TO BE INSTALLED WHEN ABOVE GROUND. LOCAL AMENDMENT TO NEC 3) RACEWAYS INSTALLED UNDER GROUND CONSIDERED WET LOCATION. ROMEX CANNOT BE INSTALLED IN WEST LOCATION. DEFENITION NEC & NEC 334.12 4) 8/3 ROMEX IS ONLY RATED FOR 40 AMP NEC 334. 80 & NEC 310.16 5) REMOVAL OF 2 B COVER TO BE ACCESSIBLE. CANNOT BE UP AGAINST PLUMBING PIPE 6) SECURE PVC PER NEC 352.30 7) GROUND CLAMP ON ONE OF THE GROUND RODS IS BROKEN 8) DEPTH OF PVC TO BE MINIMUM 18" TO TOP OF ? NEC 300.5 9) BOND GAS AND WATER PIPING PER NEC 250.104 |