Permit: T06EL02282

Parcel: 131100770


Addresses:

5634 E 24TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
08/20/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/15/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MORE THAN 360 DEG. OF BENDS IN 1" PVC
2. SEAL OPEN KNOCKOUT BOTTOM OF SERVICE PANEL
3. BONDING JUMPER TO WATER PIPE TO BE SIZED PER
NEC 250.104 & 250.66 NEEDS TO BE MIN. #4 BACK TO SERVICE PANEL.
4. COMPLETE ITEM #1 FROM PREVIOUS INSPECTION
5. ENTER 1" PVC INTO PANEL IN NEAT & WORKMANLIKE MANNER