Permit: T06EL02278

Parcel: 140180680


Addresses:

5001 S FREMONT AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/12/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
INSP. WILL WAIVE REFEE
12/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEUTRAL & GROUND WIRE MUST BE ISOLATED IN NEW DISCONNECT ABOVE DRYER OUTLET.
2. WHY IS THERE NO FAN BOX ABOVE FANS?
3. INSTALL LOCKNUT TO TERMINATE 3/4" CONNECTOR AT SERVICE PANEL.
4. SUPPORT CONDUIT WITHIN 3' OF BREAKER BOX AT DRYER
A REINSPECTION FEE IS ASSESSED

PAY REFEE AT 201 N. STONE
12/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE PROPER SPLICE DEVICE WHEN SPLICING COPPER TO ALUM. CONDUCTORS.
2. YOU CANNOT TAKE ONE LEG OFF OF 240V FEED TO DRYER OUTLET FOR 110V RECEPT & CEILING FANS.
3. 30 AMP. DRYER OUTLET MUST BE ON 30 AMP CIRCUIT BREAKER.
4. SUPPORT CONDUIT PER CODE 3' INTERVALS FOR
SCH 40 PVC
5. NO COMPLIANCE WITH NOTE #5 DO NOT CALL FOR INSP. UNTIL A LICENSED OR QUALIFIED ELECTRICIAN MAKES CORRECTIONS.
6. USE ANTI-OXIDENT COMPOUND WHEN TERMINATING ALUM. CONDUCTORS.
11/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING NOT TO CODE - NEW DRYER OUTLET INSTALLATIONS MUST BE 4-WIRE TYPE.
2. HOW DID YOU GET POWER FOR THE 110V RECEPT?
3. IMPROPER TERMINATION OF 3/4" LB INTO PANEL, USE PROPER FITTINGS.
4. CIRCUIT BREAKER TO BIG SHOULD BE 30 AMP.
5. OBTAIN THE SERVICES OF A QUALIFIED OR LICENSED ELECTRICIAN TO DO THE WORK, SUPPORT PVC PER CODE.