Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* INSP. WILL WAIVE REFEE |
|
| 12/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEUTRAL & GROUND WIRE MUST BE ISOLATED IN NEW DISCONNECT ABOVE DRYER OUTLET. 2. WHY IS THERE NO FAN BOX ABOVE FANS? 3. INSTALL LOCKNUT TO TERMINATE 3/4" CONNECTOR AT SERVICE PANEL. 4. SUPPORT CONDUIT WITHIN 3' OF BREAKER BOX AT DRYER A REINSPECTION FEE IS ASSESSED PAY REFEE AT 201 N. STONE |
|
| 12/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE PROPER SPLICE DEVICE WHEN SPLICING COPPER TO ALUM. CONDUCTORS. 2. YOU CANNOT TAKE ONE LEG OFF OF 240V FEED TO DRYER OUTLET FOR 110V RECEPT & CEILING FANS. 3. 30 AMP. DRYER OUTLET MUST BE ON 30 AMP CIRCUIT BREAKER. 4. SUPPORT CONDUIT PER CODE 3' INTERVALS FOR SCH 40 PVC 5. NO COMPLIANCE WITH NOTE #5 DO NOT CALL FOR INSP. UNTIL A LICENSED OR QUALIFIED ELECTRICIAN MAKES CORRECTIONS. 6. USE ANTI-OXIDENT COMPOUND WHEN TERMINATING ALUM. CONDUCTORS. |
|
| 11/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING NOT TO CODE - NEW DRYER OUTLET INSTALLATIONS MUST BE 4-WIRE TYPE. 2. HOW DID YOU GET POWER FOR THE 110V RECEPT? 3. IMPROPER TERMINATION OF 3/4" LB INTO PANEL, USE PROPER FITTINGS. 4. CIRCUIT BREAKER TO BIG SHOULD BE 30 AMP. 5. OBTAIN THE SERVICES OF A QUALIFIED OR LICENSED ELECTRICIAN TO DO THE WORK, SUPPORT PVC PER CODE. |