Permit: T06EL02273

Parcel: 123152840

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T06EL02273

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
01/16/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RISER CONDUIT BRACE MUST BE LISTED KIT, HOMEMADE OUT OF SMASHED EMT CONDUIT NOT APPROVED.
2. PROVIDE LADDER FOR J-BOX INSPECTION ABOVE SERVICE, USE PROPER COVER.
3. SUPPORT #6 GROUND WIRE TO WALL, BURY WIRE ALONG BUILDING OR SUPPORT TO WALL BETWEEN SERVICE & WATER HEATER.
4. INSTALL SEALING LOCKNUT AT SIDE TERMINATION OF PANEL.
5. NO POWER CLEARANCE UNTIL UNSAFE WIRING AROUND HOUSE UP TO CODE. EXPOSED ROMEX FOR SECURITY LIGHTING. ALSO, PREVIOUS PERMITS TO BE SATISFIED, SEE LOCKS, HOLDS.
6. INSTALL PERMANENT ADDRESS LABEL ON SERVICE.