Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/17/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. ONLY ONE CONDUCTOR TO GROUND CLAMP 110.3 2. LABEL BREAKERS 110.19 3. FILL UNUSED OPENING IN PANEL 110.12 4. CORRECTLY IDENTIFY GROUNDED CONDUCTOR - THIS IS A 3 WIRE SYSTEM - 200.7 5. BOND JUNCTION BOX ENCLOSURE - 250.148 6. BREAKER TO BE LISTED FOR USE BY MANUFACTURE - 110.3 7. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8 8. GROUNDING ELECTRODE TO BE BURIED BELOW SURFACE OR SECURED TO STRUCTURE. 9. PLEASE VERIFY PERMITS FOR NEW WATER HEATER AND FOR NEW WORK TO INTERIOR. 10. A RIDGID LISTED GUY BACK BRACE IS NEEDED FOR RISER. |