Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/30/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/17/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. ONLY ONE CONDUCTOR TO GROUND CLAMP 110.3
2. LABEL BREAKERS 110.19
3. FILL UNUSED OPENING IN PANEL 110.12
4. CORRECTLY IDENTIFY GROUNDED CONDUCTOR - THIS IS A 3 WIRE SYSTEM - 200.7
5. BOND JUNCTION BOX ENCLOSURE - 250.148
6. BREAKER TO BE LISTED FOR USE BY MANUFACTURE - 110.3
7. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8
8. GROUNDING ELECTRODE TO BE BURIED BELOW SURFACE OR SECURED TO STRUCTURE.
9. PLEASE VERIFY PERMITS FOR NEW WATER HEATER AND FOR NEW WORK TO INTERIOR.
10. A RIDGID LISTED GUY BACK BRACE IS NEEDED FOR RISER.