Permit: T06EL02246

Parcel: 10602302A


Addresses:

3800 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02246

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LUGS FOR SERVICE CONDUCTORS IN GUTTER
NEC 110.3B
2. SECURE STRUT INTO METER BASE TO STRUCTURE
NEC 110.13
3. BOND METER ENCLOSURE - NEC 250.92
4. BOND NEUTRAL TO SERVICE DISCONNECT ENCLOSURE
NEC 408.3C NEC 250.24C
5. IDENTIFY SERVICE DISCONNECT -- NEC 230.70
6. GROUNDING ELECTRODE AND BONDING CONDUCTORS TO EXISTING SERVICE HAVE BEEN STOLEN AND WILL NEED TO BE REPLACED/REPAIRED - NEC 250.30
7. SELF TAP SCREWS NOT ALLOWED FOR METER HUB -
NEC 250.8
8. REMOVE UNNEEDED BONDING CONDUCTOR TWO CONDUCTORS NOT ALLOWED UNDER SAME LUG UNLESS LISTED -- NEC 110.3, 110.14
12/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED TO HAVE ALL EQUIPMENT OPEN FOR INSPECTION
AND PLANS ON SITE.