Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL02246
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LUGS FOR SERVICE CONDUCTORS IN GUTTER NEC 110.3B 2. SECURE STRUT INTO METER BASE TO STRUCTURE NEC 110.13 3. BOND METER ENCLOSURE - NEC 250.92 4. BOND NEUTRAL TO SERVICE DISCONNECT ENCLOSURE NEC 408.3C NEC 250.24C 5. IDENTIFY SERVICE DISCONNECT -- NEC 230.70 6. GROUNDING ELECTRODE AND BONDING CONDUCTORS TO EXISTING SERVICE HAVE BEEN STOLEN AND WILL NEED TO BE REPLACED/REPAIRED - NEC 250.30 7. SELF TAP SCREWS NOT ALLOWED FOR METER HUB - NEC 250.8 8. REMOVE UNNEEDED BONDING CONDUCTOR TWO CONDUCTORS NOT ALLOWED UNDER SAME LUG UNLESS LISTED -- NEC 110.3, 110.14 |
|
12/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED TO HAVE ALL EQUIPMENT OPEN FOR INSPECTION AND PLANS ON SITE. |