Permit: T06EL02227

Parcel: 127041150


Addresses:

4910 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/19/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK ROUGH ELECTRIC
06/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FINISH BATHROOM
2. SECOND STRUCTURE NEED A MAIN DISCONNECTING
MEANS 225.30 & 31
3. HAVE ARCHITECT ADDRESS ARC FAULTS

OK TO CLOSE WALLS EXCEPT AS NOTED
05/07/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FILL UNUSED OPENINGS IN PANEL
2. USE APPROVED HARDWARE FOR GROUND BAR -- NOT SHEETMETAL SCREWS 250.8
CLEAN SURFACE UNDER BAR 250.12
3. PLEASE OPEN WALLS WHERE NEW WIRING HAS BEEN INSTALLED
4. A CONNECTOR IS NEEDED FOR HOOD
5. PLANS CALL FOR ARC FAULT BREAKER.