Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK ROUGH ELECTRIC |
|
| 06/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO CLOSE WALLS EXCEPT AS NOTED 1. VERIFY LIGHT AT BACK DOOR PER 210.70(A)(2) |
|
| 05/29/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH PREVIOUS ITEMS #3,6,7,8 2. EVIDENCE ON NON-CODE COMPLIANT ISSUES IN WALLS NEED TO BE RESOLVED. THIS WORK WAS DONE BY ANOTHER CONTRACTOR THAN HOLY GROUND ELECTRIC |
|
| 05/07/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL BREAKERS ON MAIN AS TO UNIT #S 2. USE APPROVED HARDWARE FOR GROUND BAR AND LISTED FOR PANEL -- SHEETMETAL THREAD SCREWS NOT ALLOWED 250.8 ALSO, CLEAN SURFACE UNDER GROUND BAR 250.12 3. IDENTIFY UNGROUNDED CONDUCTORS FOR SWITCHES PER 200.4 4. WALL NEEDS TO BE OPENED WHERE NEW WIRING WAS DONE 5. A CONNECTOR IS NEEDED AT HOOD 6. KITCHEN COUNTERTOPS TO BE GFCI PROTECTED & 2 CIRCUITS 210.8 & 210.52 7. INSTALL A GFCI OUTDOOR RECEPTACLE ON NEW LAUNDRY ROOM OUTSIDE PER 210.8 & 406.8 8. PLANS CALL FOR ARC FAULT BREAKER. |
|
| 03/09/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |