Permit: T06EL02226

Parcel: 127041150


Addresses:

4908 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/19/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK ROUGH ELECTRIC
06/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO CLOSE WALLS EXCEPT AS NOTED
1. VERIFY LIGHT AT BACK DOOR PER 210.70(A)(2)
05/29/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH PREVIOUS ITEMS #3,6,7,8
2. EVIDENCE ON NON-CODE COMPLIANT ISSUES IN WALLS NEED TO BE RESOLVED. THIS WORK WAS DONE BY ANOTHER CONTRACTOR THAN HOLY GROUND ELECTRIC
05/07/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL BREAKERS ON MAIN AS TO UNIT #S
2. USE APPROVED HARDWARE FOR GROUND BAR AND LISTED FOR PANEL -- SHEETMETAL THREAD SCREWS NOT
ALLOWED 250.8 ALSO, CLEAN SURFACE UNDER GROUND
BAR 250.12
3. IDENTIFY UNGROUNDED CONDUCTORS FOR SWITCHES
PER 200.4
4. WALL NEEDS TO BE OPENED WHERE NEW WIRING WAS DONE
5. A CONNECTOR IS NEEDED AT HOOD
6. KITCHEN COUNTERTOPS TO BE GFCI PROTECTED & 2 CIRCUITS 210.8 & 210.52
7. INSTALL A GFCI OUTDOOR RECEPTACLE ON NEW LAUNDRY ROOM OUTSIDE PER 210.8 & 406.8
8. PLANS CALL FOR ARC FAULT BREAKER.
03/09/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*