Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 12/07/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR #12 WIRING - #14 USED 2. PLAN CALLS FOR 20 AMP GFCI BREAKER NOT INSTALLED 3. LABEL THIS CIRCUIT IN PANEL 4. EXPOSE ALL WIRES IN THIS CIRCUIT FOR INSPECTION |