Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 2. USE CORRECT COLOR CONDUCTORS #10 AND SMALLER IN RACEWAY. 3. USE CORRECT SIZED WIRE NUT FOR CONDUCTORS - ALSO, THIS CONNECTION IS AN UNGROUNDED NEUTRAL SYSTEM. 4. BOND JUNCTION BOX 5. TIGHTEN LOOSE FITTINGS. |
|
| 12/01/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE RECALL AFTER CROSS OVER |
|
| 11/16/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING SPACE AS DISCUSSED 2. PLEASE VERIFY OTHER PERMIT FOR WORK BEING DONE - NEW |
|
| 11/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE. 2. VERIFY PERMIT FOR NEW A/C 3. PLEASE BOND TO INTERIOR SIDE OF WATER VALVE. OK GROUND RODS. |