Permit: T06EL02207

Parcel: 123030380


Addresses:

1616 N TREAT AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ANSWER AT DOOR
DOG LOOSE IN BACKYARD
TIE UP & RECALL
11/15/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) TIGHTEN MAST STRAPS ON ROOF
2) EQUIPMENT GROUND ? IN CONDUIT TO GROUND J-BOX (#10 COPPER)
11/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. MAKE PANEL DIRECTORY CLEAR, CORRECT AND LEGIBLE.
2. SERVICE AND MAST STILL NOT SECURE.
3. J-BOX GROUND TO BE RAN WITH CONDUCTORS IN RACEWAY.
4. BRANCH CKT RACEWAY STILL SLOPPY

WILL PAY REINSPECTION FEE - IF ALL NOT CORRECT NEXT INSPECTION.
11/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1) IDENTIFY ALL BRANCH CKT'S CORRECTLY-NEC 408.4
2) MAST NOT SECURE TO STRUCTURE AND ADD 2ND STRAP AT TOP-NEC 110.13, NEC 230.28, USE LSTED GUY KIT
3) SERVICE NOT SECURE TO STRUCTURE-NEC 110.13
4) BRANCH CKT RACEWAY TO J-BOX IS LOOSE, FITTINGS NOT ON ALL THE WAY, NOT SQUARE ETC.-NEC 110.12 AND USE PROPER SIZE STRAPS FOR RACEWAY -NEC 110.3
5) PROVIDE A PROPERLY SIZED EQUIPMENT GROUND TO J-BOX GROUND ENCLOSURE AND PROPERLY TERMINATE GROUNDS-NEC 250.130
6) MOUNTING AND SECURING OF ALL EQUIPMENT TO GO INTO SOLID STRUCTURE MATERIAL-NOT JUST STUCCO OR ROOF SHEATHING