Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ANSWER AT DOOR DOG LOOSE IN BACKYARD TIE UP & RECALL |
|
| 11/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) TIGHTEN MAST STRAPS ON ROOF 2) EQUIPMENT GROUND ? IN CONDUIT TO GROUND J-BOX (#10 COPPER) |
|
| 11/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. MAKE PANEL DIRECTORY CLEAR, CORRECT AND LEGIBLE. 2. SERVICE AND MAST STILL NOT SECURE. 3. J-BOX GROUND TO BE RAN WITH CONDUCTORS IN RACEWAY. 4. BRANCH CKT RACEWAY STILL SLOPPY WILL PAY REINSPECTION FEE - IF ALL NOT CORRECT NEXT INSPECTION. |
|
| 11/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1) IDENTIFY ALL BRANCH CKT'S CORRECTLY-NEC 408.4 2) MAST NOT SECURE TO STRUCTURE AND ADD 2ND STRAP AT TOP-NEC 110.13, NEC 230.28, USE LSTED GUY KIT 3) SERVICE NOT SECURE TO STRUCTURE-NEC 110.13 4) BRANCH CKT RACEWAY TO J-BOX IS LOOSE, FITTINGS NOT ON ALL THE WAY, NOT SQUARE ETC.-NEC 110.12 AND USE PROPER SIZE STRAPS FOR RACEWAY -NEC 110.3 5) PROVIDE A PROPERLY SIZED EQUIPMENT GROUND TO J-BOX GROUND ENCLOSURE AND PROPERLY TERMINATE GROUNDS-NEC 250.130 6) MOUNTING AND SECURING OF ALL EQUIPMENT TO GO INTO SOLID STRUCTURE MATERIAL-NOT JUST STUCCO OR ROOF SHEATHING |