Permit: T06EL02204

Parcel: 126190090


Addresses:

4365 E WARE ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WHEN THE GROUNDING ELECTRODE PASSES THROUGH THE END OF METAL CONDUIT, THERE MUST BE A GROUND BUSHING AT THE END OF THE CONDUIT AND THE GROUND WIRE MUST ALSO RUN THROUGH GROUND BUSHINGS LUG, TO REDUCE CHOKE EFFECT NEC 250.4(E)
11/17/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*