Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHEN THE GROUNDING ELECTRODE PASSES THROUGH THE END OF METAL CONDUIT, THERE MUST BE A GROUND BUSHING AT THE END OF THE CONDUIT AND THE GROUND WIRE MUST ALSO RUN THROUGH GROUND BUSHINGS LUG, TO REDUCE CHOKE EFFECT NEC 250.4(E) |
|
| 11/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* |