Permit: T06EL02175

Parcel: 127121700


Addresses:

5732 E HOLMES ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/16/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/09/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SEE CALCULATIONS FOR 310.15 NUMBER OF CURRENT CARRYING CONDUCTORS. 30 AMP BREAKERS OK. WHAT IS LOAD OF AC & DRYER? ARE THEY GREATER OR LESS THAN 26.24 AMPS? #6 WIRE TO BE INSTALLED ON A 50 AMP BREAKER. WHAT IS LOAD OF HOUSE PANEL? IS IT GREATER OR LESS THAN 49.2 AMPS.
2. CHECK TIGHTNESS OF CONDUCTOR TERMINATION.
3. SUPPORT CONDUIT ACROSS ROOF.
4. SUPPORT BOND CONDUCTOR ACROSS ROOF.
5. TIGHTEN LOOSE FITTINGS ON ROOF.
11/02/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) INSULATION TO BE EQUAL OR GREATER FOR SPLICES-NEED RUBBER TAPE
2) CLEAN SURFACE UNDER LUG-GROUND
3) PLEASE VERIFY DERATING OF CONDUCTORS PER 310.15 AND FOR AMBIENT TEMPERATURE 310.16
4) IDENTIFY GROUNDED CONDUCTOR ? LUG
5) INSTALL ALL STRANDS OF CONDUCTOR UNDER LUGS
6) FILL UNUSED OPENINGS IN PANEL
7) RISER SUPPORT TO BE 1/4" MINIMUM
8) OK WATER AND GAS BONDS