Permit: T06EL02174

Parcel: 12611151A


Addresses:

4413 E BROADWAY BL

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CONDITION OF SERVICE EQUIPMENT IS DETERIORATED. WE ALSO HAVE NUMEROUS CODE VIOLATIONS
2) LABELS TO BE SCREWED OR RIVITED TO EQUIPMENT
11/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE REMOVE ZIP CORD WIRING
2) WE HAVE A BURNT AND DAMAGED RECEPTACLE
3) ATTACH BOXES TO WALL
4) CLEAN EXCESS PAINT OUT OF DEVICES
5) REPLACE BROKEN FACE PLATE
6) TAPE IS NOT AN APPROVED HANDLE TIE
7) LABEL BREAKERS
8) BOXES TO BE LISTED FOR WET LOCATION, ALSO FITTINGS
9) CONDUIT AND LB SEPERATED
10) EQUIPMENT AT SERVICE IN DETERIORATING CONDITION
11) A PERMANENT METAL ADDRESS LABEL IS NEEDED
12) KITCHEN RECEPTACLE TO BE GFCI PROTECTED
13) NEON INTERIOR PORATBLE SIGN NOT LISTED 600.3