Permit: T06EL02169

Parcel: 125090480


Addresses:

2710 E 10TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T06EL02169

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) NO ACCESS-INTERIOR INSPECTIONS AND GROUNDING OF INTERIOR J-BOX TO BE DONE AT LATER DATE
11/01/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT/STRAP EMT IN ATTIC -- NEC 358.30
2. CONDUCTORS IN RACEWAYS TO BE DERATED - NEC 310.15
3. DIFFERENT SIZE CONDUCTORS NOT ALLOWED UNDER SAME TERMINATION IN SERVICE -- NEC 110.14
4. IDENTIFY PANEL DIRECTORY (CORRECTLY) -- NEC 408.4
5. DRIVE GROUND RODS FLUSH - NEC 250.53 G
6. INSTALL L.B COVER ABOVE PANEL
7. CLOSE UP AND PROPERLY GROUND INTERIOR J-BOX
NEC 110, 250
8. ADD ALL NEW INTERIOR WIRING TO PERMIT FOR INSPECTION.