Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL02169
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) NO ACCESS-INTERIOR INSPECTIONS AND GROUNDING OF INTERIOR J-BOX TO BE DONE AT LATER DATE |
|
| 11/01/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT/STRAP EMT IN ATTIC -- NEC 358.30 2. CONDUCTORS IN RACEWAYS TO BE DERATED - NEC 310.15 3. DIFFERENT SIZE CONDUCTORS NOT ALLOWED UNDER SAME TERMINATION IN SERVICE -- NEC 110.14 4. IDENTIFY PANEL DIRECTORY (CORRECTLY) -- NEC 408.4 5. DRIVE GROUND RODS FLUSH - NEC 250.53 G 6. INSTALL L.B COVER ABOVE PANEL 7. CLOSE UP AND PROPERLY GROUND INTERIOR J-BOX NEC 110, 250 8. ADD ALL NEW INTERIOR WIRING TO PERMIT FOR INSPECTION. |