Permit: T06EL02153

Parcel: 115023900


Addresses:

316 E ELM ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/15/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. MOVE LUGS TO OVERHEAD POSITION AS INDICATED IN METER SECTION -- NEC 110.3 (B)
2. IDENTIFY PANEL DIRECTORY -- NEC 408.4
3. USE LISTED MAST BRACE (STIFF ARMS OR GUY KIT) -
NEC 110.3(A) AND SECURE INTO STRUCTURE, NOT ROOF SHEATING -- NEC 230.28
4. SECURE ROMEX GOING INTO PANEL -- NEC 334.30
5. BOND EXPOSED DRAIN PIPE IN LAUNDRY - NEC 250.104 (A, B)