Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/01/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. MOVE LUGS TO OVERHEAD POSITION AS INDICATED IN METER SECTION -- NEC 110.3 (B) 2. IDENTIFY PANEL DIRECTORY -- NEC 408.4 3. USE LISTED MAST BRACE (STIFF ARMS OR GUY KIT) - NEC 110.3(A) AND SECURE INTO STRUCTURE, NOT ROOF SHEATING -- NEC 230.28 4. SECURE ROMEX GOING INTO PANEL -- NEC 334.30 5. BOND EXPOSED DRAIN PIPE IN LAUNDRY - NEC 250.104 (A, B) |