Permit: T06EL02142

Parcel: 107081720


Addresses:

807 W JACINTO ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/17/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/09/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) CALL FOR FINAL AFTER SWITCH OVER COMPLETE, SEAL ROOF FLASHING
11/07/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BURY GROUNDING ELECTRODE/BOND CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE -- NEC 250.64 (B)
2. USE A LISTED GUY KIT OR STIFF ARMS TO SUPPORT/BRACE MAST AND SECURE IT TO STRUCTURE - NOT JUST ROOF SHEATHING -- NEC 230.28, NEC 110.3 A 2
3. GROUND RODS TO BE A MINIMUM OF 6' APART -
NEC 250.53 (B)
4. IDENTIFY SERVICE NEUTRAL WHERE IT COMES OUT OF WEATHERHEAD AND AT SERVICE TERMINATION -- NEC 200