Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/09/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER SWITCH OVER COMPLETE, SEAL ROOF FLASHING |
|
| 11/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BURY GROUNDING ELECTRODE/BOND CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE -- NEC 250.64 (B) 2. USE A LISTED GUY KIT OR STIFF ARMS TO SUPPORT/BRACE MAST AND SECURE IT TO STRUCTURE - NOT JUST ROOF SHEATHING -- NEC 230.28, NEC 110.3 A 2 3. GROUND RODS TO BE A MINIMUM OF 6' APART - NEC 250.53 (B) 4. IDENTIFY SERVICE NEUTRAL WHERE IT COMES OUT OF WEATHERHEAD AND AT SERVICE TERMINATION -- NEC 200 |