Permit: T06EL02141

Parcel: 119211140


Addresses:

1670 W CIRCLE A DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/15/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SPLICES IN J-BOX NOT SECURE - BLUE WIRE NUT NOT MAKING A GOOD WIRE TO WIRE CONTACT INSIDE.
SUGGEST USING INSULATED MULTI-TAP LUGS DUE TO CONDUCTORS COMING OUT OF HOUSE TO SHORT.
2. ADD SERVICE UPGRADE TO PERMIT
11/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 2" RISER MISSING 2 STRAPS
2. KEARNEYS IN J-BOX VERY POORLY TAPED
EXPOSED KEARNEY ON HOT LEG
TAPE KEARNEYS WITH INSULATING TAPE THEN BLACK TAPE COVER ALL METAL.
3. CAN SEE DAYLIGHT ON 3/4" EMT FITTINGS ON TOP OF J-BOX NEEDS TO BE SEALED.
11/01/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES LAST INSPECTION, MUST COMPLY
10/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ELECTRIC SERVICE NOT INSTALLED PER CODE.

OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN TO UPGRADE SERVICE, ADD UPGRADE TO PERMIT.

2. INSTALL SMOKE DETECTORS IN SLEEPING AREAS, MAKE SURE ALL RECEPTS, LIGHT FIXTURES, OUTLET INTACT.