Permit: T06EL02138

Parcel: 124061990


Addresses:

1223 E 10TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02138

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALL CORRECTIONS NOT COMPLETE SEE ITEMS FROM 11/14/06
11/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*


1. CONDUIT IS NOT INSTALLED IN A NEAT AND WORKMANLIKE MANNER.
2. BONDING BUSHING NEEDED WHERE NIPPLE ENTERS THROUGH CONCENTRIC KNOCKOUTS.
3. E.M.T CONNECTOR IS CROSS THREADED AT LB
4. E.M.T CONNECTOR IS LOOSE AT 6X6X4 J-BOX
5. EXPOSE GROUND RODS.
6. E.M.T IS NOT ACCEPTABLE FOR U.G USE
7. GAS BOND IS LOOSE.
11/08/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*