Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL CORRECTIONS NOT COMPLETE SEE ITEMS FROM 11/14/06 |
|
| 11/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUIT NOT INSTALLED IN A WORKMAN LIKE MANNER. 2. BOND BUSHING REQ'D AT CENTRIC KNOCKOUTS. 3. EMT CONNECTOR CROSS THREADED 4. EMT CONNECTORS LOOSE 5. EXPOSE GROUND RODS. 6. EMT NOT ACCEPTABLE FOR U.G USE 7. GAS BOND IS LOOSE |
|
| 11/08/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |