Permit: T06EL02135

Parcel: 135074550

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02135

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PREVENT OBJECTIONABLE CURRENT - WE HAVE PARALLEL PATHS OF GROUND 250.6
2. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN LIVE GUTTER OR/AND TERM CAN.
3. SEPARATE GROUNDS & NEUTRAL AT SUB-PANEL.
4. BREAKER TO BE LISTED FOR USE BY MANUFACTURER.
5. CONDUCTOR TO BE COLOR CODED PER CITY AMENDMENTS.
6. INSTALL ALL STRANDS UNDER TERMINAL LUGS.
7. CORRECTLY LABEL CIRCUIT DIRECTORY.
8. TIGHTEN LOOSE FITTINGS.
11/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMIT NEEDS TO INCLUDE A SUITE NUMBER