Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL02135
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PREVENT OBJECTIONABLE CURRENT - WE HAVE PARALLEL PATHS OF GROUND 250.6 2. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN LIVE GUTTER OR/AND TERM CAN. 3. SEPARATE GROUNDS & NEUTRAL AT SUB-PANEL. 4. BREAKER TO BE LISTED FOR USE BY MANUFACTURER. 5. CONDUCTOR TO BE COLOR CODED PER CITY AMENDMENTS. 6. INSTALL ALL STRANDS UNDER TERMINAL LUGS. 7. CORRECTLY LABEL CIRCUIT DIRECTORY. 8. TIGHTEN LOOSE FITTINGS. |
|
11/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMIT NEEDS TO INCLUDE A SUITE NUMBER |