Permit: T06EL02134

Parcel: 112073980


Addresses:

2561 N STEWART AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MESSAGE DID NOT COME THROUGH IVR
ITEMS #1, 7, 8 NOT COMPLETE
11/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1) SERVICE DROP DOES NOT HAVE PROPER ROOF CLEARANCE OVER ROOF-NEC 230.24A
2) SECURE GROUND ELETRODE CONDUCTOR TO STRUCTURE NOT RACEWAYS-NEC 250.64, 300.11B
3) RELOCATE SERVICE CONDUCTORS TO OVERHEAD POSITION AS INDICATED IN METER SECTION-NEC 110.3B
4) APPLAN AN OXIDATION INHIBITOR ON ALL ALUMINIUM TERMINATIONS-NEC 110.13
5) STRUT NEEDS TO BE SUCRED TO STRUCTURE AND TIGHTEN STRUT CLAMPS NEC 110.13
6) TIGHTEN GAS BOND CLAMP NEC 250.4A5
7) BRANCH CKT CONDUCTORS IN RACEWAY TO BE DERATED-NEC 310.15
8) PROVIDE PROPERLY SIZED EQUIPMENT GROUND TO GUTTER-NEC 250.122 AND 250.148
9) GUTT TO BE RAINTITE-110.3
10) NEED PERMIT/INSPECTION FOR NEW A/C
11) TIGHTEN ALL RACEWAY FITTINGS-NEC 110.12, 358.42
12) LOWER SINGLE GANG WEATHER PROOF J-BOX IS OVER FILLED-NEC 314.16 AND NEEDS CONNECTORS FOR ROMEX-NEC 314.17
13) PROTECT CABLES ENTERING GUTTER-BNEC 334.15
14) MAX 15 AMP ON 14 GA WIRE-NEC 310