Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* AT BUILDING DISCONNECT 1. GROUNDING ELECTRODE CONDUCTORS HAVE BEEN CUT AND NEED TO BE REPLACED/REPAIRED. 2. GROUNDS AND NEUTRALS TO BE SEPARATED IN DISCONNECT AND SUBPANEL. DO NOT BOND NEUTRAL TO THESE ENCLOSURES -- USE EQUIPMENT GROUND TO GROUND THESE ENCLOSURES (NEUTRAL "FLOATS") |