Permit: T06EL02120

Parcel: 116180500


Addresses:

218 N MELROSE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. KITCHEN CKT. ENTERING PANEL NEEDS PROPER CONNECTOR AND SEAL OPENING FROM WEATHER.
2. J-BOX ABOVE PANEL NEEDS PROPERLY SIZED EQUIPMENT GROUND TO GROUND IT.
3. EQUIPMENT GROUND TO AC IS CUT - DO NOT USE NEUTRAL (WHITE) TO GROUND EQUIPMENT.
4. SUB-PANEL NEUTRAL TO BE IDENTIFIED WHITE - NOT GREEN
5. BURY G.E.C BETWEEN GROUND RODS AT LEAST 12" OR SECURE TO STRUCTURE.
6. IF AC WIRING IS NEW, ADD IT TO PERMIT -- OTHERWISE MAKE SURE IT IS GROUNDED PROPERLY.