Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. KITCHEN CKT. ENTERING PANEL NEEDS PROPER CONNECTOR AND SEAL OPENING FROM WEATHER. 2. J-BOX ABOVE PANEL NEEDS PROPERLY SIZED EQUIPMENT GROUND TO GROUND IT. 3. EQUIPMENT GROUND TO AC IS CUT - DO NOT USE NEUTRAL (WHITE) TO GROUND EQUIPMENT. 4. SUB-PANEL NEUTRAL TO BE IDENTIFIED WHITE - NOT GREEN 5. BURY G.E.C BETWEEN GROUND RODS AT LEAST 12" OR SECURE TO STRUCTURE. 6. IF AC WIRING IS NEW, ADD IT TO PERMIT -- OTHERWISE MAKE SURE IT IS GROUNDED PROPERLY. |