Permit: T06EL02114

Parcel: 135053000

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
11/02/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
10/31/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
DRIVE RODS FLUSH OR BELOW FINISHED GRADE PER NEC
10/27/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. BOND TO INTERIOR SIDE OF WATER PIPING.
2. PROTECT CONDUCTOR FROM SHARP METAL EDGE IN BACK OF PANEL.
3. LABEL CIRCUIT BREAKERS.
4. DO NOT FORK/SPLIT CONDUCTOR
5. RISER SUPPORT HARDWARE TO BE 1/4" MINIMUM -- NOT DRY WALL SCREW OR SMALL ANCHOR.