Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2007 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 01/05/2007 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LADDER TO SEE ROOF CONNECTIONS ON GUY BACK SUPPORTS. 2. NEED TO USE A LISTED APPROVED TYPE OF GUY BACK SUPPORT SUCH AS RIGID THREADED CONDUIT WITH THREADED EYE LETS CONNECTED TO RISER DUE TO HEIGHT OF RISER AND LENGTH OF DROP. 3. NEED INTERIOR INSPECTED ON CONNECTION OF WIRING. |
|
| 12/29/2006 | ELECTRIC - SERVICE RELOCATION | Cancelled | IVRS - RI canceled | |
| 12/28/2006 | ELECTRIC - SERVICE RELOCATION | Cancelled | IVRS - RI canceled |