Permit: T06EL02101

Parcel: 122091500


Addresses:

4102 E LINDEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02101

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/03/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CANNOT ENTER ABOVE BREAKER INTO TOP SECTION OF PANEL.
2. USE UV RATED TY'S WRAPS
3. CHASE NIPPLE NOT AN APPROVED FITTING WITH LB
4. JUNCTION BOXES NOT ALLOWED TO HAVE HOLE DRILLED INTO.
5. CANNOT GROUND OLD 3 WIRE UNGROUNDED SYSTEM TO BOX.