Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL02089
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/03/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IS THERE A PERMIT FOR NEW AC WHICH APPEARS TO BE CONNECTED TO SERVICE ALREADY. 2. #12 WIRE ON 30 AMP 2 POLE CIRCUIT 3. TIGHTEN CONNECTOR WHERE GROUNDS ENTER THRU BOTTOM OF SERVICE. 4. SEE NOTE ON PANEL LABEL "LOAD CONDUCTORS NOT TO EXIT THROUGH TOP END WALL" ALSO, TOP ENTRY NOT WEATHER APPROVED. 5. WHEN YOU HAVE MORE THAN 3 HOT CONDUCTORS IN ONE CONDUIT, YOU HAVE TO DERATE PER TABLE 310-15, B, 2, 2002 NEC, DERATING TABLE 6. DRIVE GROUND RODS TO GRADE OR BELOW. |