Permit: T06EL02084

Parcel: 107143500


Addresses:

2455 N LOS ALTOS AV

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
11/14/2007 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
05/29/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE DISCONNECT NOT RATED FOR OUTDOOR USE.
2. POLE MTD - SERVICE IS OLD 30 AMP. OR 60 AMP. OUTDATED UPGRADE TO CURRENT CODES, NO LOAD CONNECTED - SPECIFY WHAT SERVICE IS FOR?
3. ALSO, TO CLOSE TO POOL, MUST BE 22.5' CLEARANCE FROM SERVICE CONDUCTORS PER 680 NEC