Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 05/29/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE DISCONNECT NOT RATED FOR OUTDOOR USE. 2. POLE MTD - SERVICE IS OLD 30 AMP. OR 60 AMP. OUTDATED UPGRADE TO CURRENT CODES, NO LOAD CONNECTED - SPECIFY WHAT SERVICE IS FOR? 3. ALSO, TO CLOSE TO POOL, MUST BE 22.5' CLEARANCE FROM SERVICE CONDUCTORS PER 680 NEC |