Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FILL UNUSED OPENING IN METAL SOCKET & BOND NIPPLE. 2. FILL UNUSED PORTION IN BACK OF PANEL WITH NON-COMBUSTIBLE PRODUCT. 3. SEPARATE AND TERMINATE GROUNDING EQUIPMENT CONDUCTORS. 4. CORRECTLY IDENTIFY GROUNDED CONDUCTOR OF 3 WIRE FEEDER. 5. PLEASE PROVIDE DRIP LOOP FOR M/C CABLE USED OUTDOORS. 6. PLEASE VERIFY WATER BOND. 7. USE SPLICE CONNECTOR LISTED FOR COPPER TO ALUMINUM CONNECTIONS. 8. INSTALL ALL STRAND UNDER BREAKER LUG. 9. A PERMANENT ADDRESS LABEL IS NEEDED. |