Permit: T06EL02054

Parcel: 13012304B


Addresses:

3670 E ELLINGTON PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FILL UNUSED OPENING IN METAL SOCKET & BOND NIPPLE.
2. FILL UNUSED PORTION IN BACK OF PANEL WITH NON-COMBUSTIBLE PRODUCT.
3. SEPARATE AND TERMINATE GROUNDING EQUIPMENT CONDUCTORS.
4. CORRECTLY IDENTIFY GROUNDED CONDUCTOR OF 3 WIRE FEEDER.
5. PLEASE PROVIDE DRIP LOOP FOR M/C CABLE USED OUTDOORS.
6. PLEASE VERIFY WATER BOND.
7. USE SPLICE CONNECTOR LISTED FOR COPPER TO ALUMINUM CONNECTIONS.
8. INSTALL ALL STRAND UNDER BREAKER LUG.
9. A PERMANENT ADDRESS LABEL IS NEEDED.