Permit: T06EL02032

Parcel: 113021530


Addresses:

1051 E WEYMOUTH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SHEETMETAL SCREWS NOT ALLOWED FOR GROUND BAR
REFEE NEXT INSPECTION IF NOT CORRECT
12/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SELF TAP SCREWS NOT ALLOWED ON GROUND BAR
2. 2 CONDUCTORS NOT ALLOWED UNDER SAME LUG UNLESS LISTED FOR IT
3. INSTALL PANEL COVERS.

PAY REINSPECTION FEE
11/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SHEETMETAL/SELF TAP SCREWS NOT ALLOWED FOR GROUND CONNECTION -- NEC 250.8
2. REMOVE PAINT UNDER CONNECTION - NEC 250.12
11/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CORRECTIONS HAVE NOT BEEN MADE. HAVE A QUALIFIED LICENSED ELECTRICAL CONTRACTOR COMPLETE WORK
DO NOT CALL UNTIL CORRECTIONS HAVE BEEN PROPERLY MADE OR A REINSPECTION FEE WILL BE CHARGED NEXT TRIP.
11/01/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPER PROVISIONS MUST BE MADE TO TERMINATE FEEDERS -- CAN'T USE ONE CONDUCTOR TO CARRY BOTH LOADS.
2. EQUIPMENT GROUND TO GROUND ENCLOSURES & EQUIPMENT GROUNDS IN SUB-PANELS - NEUTRALS TO "FLOAT"
3. IN DISCONNECTS - CAN'T HAVE TWO DIFFERENT CONDUCTORS UNDER SAME TERMINATION (FEEDER NEUTRAL AND GROUNDING ELECTRODE CONDUCTOR).
4. PROVIDE A NEUTRAL TO SUB-PANELS
10/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE HAVE PLANS OR ELECTRICIAN PRESENT
2. VIOLATION NOTICE TO BE ON SITE
3. WORK TO BE INSTALLED PER 2002 NEC