Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SHEETMETAL SCREWS NOT ALLOWED FOR GROUND BAR REFEE NEXT INSPECTION IF NOT CORRECT |
|
| 12/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SELF TAP SCREWS NOT ALLOWED ON GROUND BAR 2. 2 CONDUCTORS NOT ALLOWED UNDER SAME LUG UNLESS LISTED FOR IT 3. INSTALL PANEL COVERS. PAY REINSPECTION FEE |
|
| 11/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SHEETMETAL/SELF TAP SCREWS NOT ALLOWED FOR GROUND CONNECTION -- NEC 250.8 2. REMOVE PAINT UNDER CONNECTION - NEC 250.12 |
|
| 11/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECTIONS HAVE NOT BEEN MADE. HAVE A QUALIFIED LICENSED ELECTRICAL CONTRACTOR COMPLETE WORK DO NOT CALL UNTIL CORRECTIONS HAVE BEEN PROPERLY MADE OR A REINSPECTION FEE WILL BE CHARGED NEXT TRIP. |
|
| 11/01/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPER PROVISIONS MUST BE MADE TO TERMINATE FEEDERS -- CAN'T USE ONE CONDUCTOR TO CARRY BOTH LOADS. 2. EQUIPMENT GROUND TO GROUND ENCLOSURES & EQUIPMENT GROUNDS IN SUB-PANELS - NEUTRALS TO "FLOAT" 3. IN DISCONNECTS - CAN'T HAVE TWO DIFFERENT CONDUCTORS UNDER SAME TERMINATION (FEEDER NEUTRAL AND GROUNDING ELECTRODE CONDUCTOR). 4. PROVIDE A NEUTRAL TO SUB-PANELS |
|
| 10/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE HAVE PLANS OR ELECTRICIAN PRESENT 2. VIOLATION NOTICE TO BE ON SITE 3. WORK TO BE INSTALLED PER 2002 NEC |