Permit: T06EL02029


Addresses:

2448 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL02029

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY BRANCH CKT. BREAKER - NEC 408.4
2. PROVIDE AN EQUIPMENT GROUND FOR BRANCH CKT
NEC 250.122
3. PROVIDE 36" CLEAR SPACE IN FRONT OF SERVICE
NEC 110.26