Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* OK SUBJECT TO BELOW 1. OK TO RELEASE TEMP SERVICE ONE DEMO PERMIT RELEASED. 2. SET UP GFI BELOW SERVICE FOR TEMP POWER AND ALL OTHER CIR'S TO BE REMOVED. |
|
| 10/09/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL WORKING SMOKE DETECTORS 2. FUSE HOLDERS & SWITCH COVER NOT INSTALLED PROPERLY IN KITCHEN. ALSO, FLUORESCENT FIXTURE ABOVE SINK NOT WIRED PER CODE, EXPOSED WIRING. 3. RECEPTACLE BY SINK SHOULD BE GFI TYPE. 4. WIRE THE DISCONNECT ON WEST SIDE OF UNIT PER CODE IF USED. WHY ARE THE FEEDERS TO INSIDE CAPPED OFF? 5. STORAGE ON WEST SIDE OF BUILDING NOT WIRED PER CODE, EXPOSED WIRING. 6. WHERE IS THE SERVICE? OBTAIN THE SERVICES OF A QUALIFIED OR LICENSED ELECTRICIAN TO DO WORK. 7. WIRE COOLER PER CODE. |