Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/08/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BONDING BUSHING ON OFFSET NIPPLE PER ART. 250 2. INSTALL BUSHING AT 2 1/2" KNOCKOUT PER ART. 110.3 3. INSTALL GROUNDING ELECTRODE SYSTEM. 4. BOND GAS PER ART. 250 & WATER 5. INSTALL COMPRESSION E.M.T CONNECTOR FOR PANEL PENETRATION INTO THE SIDE OF PANEL. 6. INSTALL ANTI-OXIDATION PASTE ON ALL ALUM. TERMINATIONS. 7. SECURE #4 CONDUCTOR BELOW PANEL (WATER BOND) 8. LOCKNUT AT E.M.T CONNECTOR NEEDS TO BE TIGHT. 9. USE OUTDOOR WEATHERPROOF COVER AT WEATHERPROOF J-BOX. 10. INSTALL MISSING SCREW AT PANEL DEADFRONT COVER. 11. LABEL ALL BREAKERS. 12. POOL LIGHT TO BE GFCI PROTECTED PER ART. 680 13. WIRING THROUGH BLOCK IS NOT INSTALLED PER N.E.C. |