Permit: T06EL01927

Parcel: 10820051G


Addresses:

4036 N 1ST AV


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01927

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
09/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. DRIVE GROUND RODS FLUSH TO GRADE.
2. INSTALL ALL DEAD FRONT COVERS
3. ALL POWER CORDS TO BE LISTED FOR EXTRA HARD USAGE AND PROTECTED FROM PHYSICAL PROTECTION -- NEC 525.20
4. GROUNDING ELECTRODE CONDUCTORS DAMAGED/FRYED
5. POWER CORDS TO HAVE PROPER OVERCURRENT PROTECTION -- NEC 310, 400
6. INSTALL BULB PROTECTION AS NEEDED 525.21 (B)
7. TERMINATIONS IN ALL PANELS TO BE TERMINATED PROPERLY NEC 110.19
8. ALL RECEPTACLES TO HAVE GFI PROTECTION AS REQUIRED IN NEC 525.23 AND REPLACE IN CRACKED/DAMAGED COVERS.
9. ALL DISCONNECTING MEANS TO COMPLY WITH NEC 525.21(A) ROLLER DERBY ETC.
10. IDENTIFY PANEL DIRECTORIES - 408.4
11. WIRING INSIDE TENTS AND CONCESSIONS TO BE SECURE AND PROTECTED -- NEC 525.21(B)
12. CORRECTLY INSTALL ALL EQUIPMENT COVERS.
09/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH WIRING (ALL) PRIOR TO INSPECTION
2. INSTALLATION TO COMPLY WITH ALL PROVISIONS OF
2002 NEC ART. 525 IT APPEARS THERE MAY BE VIOLATIONS IN THE INSTALLATION.