Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. TIGHTEN BOND CLAMP SCREWS -- NEC 110 2. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE -- NEC 250.64 3. EXPOSE GROUND RODS 4. MAKE SURE PANEL DIRECTORY IS CORRECTLY IDENTIFIED -- NEC 408.4 |