Inspection History Details
Inspection Status: Cancelled
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 09/20/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE 110.26 2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 3. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT. 4. ONLY ONE GROUNDED CONDUCTOR TO A TERMINATION. 5. NM CABLES ON EXTERIOR ENTRANCE TO PANEL TO BE IN A NON-FLEXIBLE RACEWAY. 6. TIGHTEN LOOSE FITTINGS. |