Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 10/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/16/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. TERMINAL GROUNDING ELECTRODE CONDUCTOR IN SERVICE. 2. BOND CLAMPS ARE LOOSE 3. EXPOSE SECOND GROUND ROD 4. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE UP THE WALL. 5. STRUT CHANNEL NOT PROPERLY SECURED TO WALL (LOOSE) 6. SERVICE CONDUCTORS NEED 18" DEPTH AT SERVICE 7. SECURE SERVICE TO STRUCTURE 8. NEED WARNING RIBBON MINIMUM 12" ABOVE SERVICE RACEWAY. 9. HOW WILL SERVICE RISER AT POLE BE BONDED? |