Permit: T06EL01880

Parcel: 123071130


Addresses:

2034 E MABEL ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/16/2007 ELECTRIC - INTERMEDIATE Approved
10/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/16/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. TERMINAL GROUNDING ELECTRODE CONDUCTOR IN SERVICE.
2. BOND CLAMPS ARE LOOSE
3. EXPOSE SECOND GROUND ROD
4. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE UP THE WALL.
5. STRUT CHANNEL NOT PROPERLY SECURED TO WALL (LOOSE)
6. SERVICE CONDUCTORS NEED 18" DEPTH AT SERVICE
7. SECURE SERVICE TO STRUCTURE
8. NEED WARNING RIBBON MINIMUM 12" ABOVE SERVICE RACEWAY.
9. HOW WILL SERVICE RISER AT POLE BE BONDED?