Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) NOTICE TO OWNER: PERMANENTLY MARK SERVICES 1, 2 & 3 |
|
| 10/09/2006 | ELECTRIC - FINAL | Denied | 1. REMOVE GROUND ON #1 2. ID PNL 3. NOT GROUPED -- WINDOW & AC SEPARATE 4TH METER APPROX. 8' AWAY 4. CONDUIT ON ROOF NOT SUPPORTED. 5. WHERE SPLICE MADE TO LAUNDRY -- IS THERE COMBINED PANEL OR J-BOX CONTAINING BOTH SYSTEMS APT & LAUNDRY? |
|
| 09/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE UNNEEDED BONDING CONDUCTOR IN SERVICE RACEWAY BETWEEN GUTTER & NEW METER THAT CREATE A CODE VIOLATION -- NEC 250.6 2. IDENTIFY PANEL DIRECTORY -- NEC 408.4 3. SERVICE DISCONNECTS TO BE "GROUPED" TOGETHER? NEC 230.72 4. CAN'T FIND WIRING TO LAUNDRY ROOM? NOT FINISHED? |