Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2007 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 01/12/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TEP TIE IN |
|
| 01/09/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY WATER PIPE BOND 2. INSTALL ROOF JACK 3. MARKER NOT APPROVED FOR ADDRESS - USE OF PERMANENT LABEL, MUST BE SCREWED OR RIVITED TO ENCLOSURE. |
|
| 09/27/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE FLUSH WITH GRADE. 2. SUPPORT #4 BARE TO WALL BELOW PANEL. 3. BOND WATER & GAS PIPING 4. INSTALL ROOF JACK 5. WIRING FOR LOADS NOT ALLOWED TO BE IN SHIELDED AREA ABOVE BUSS AT TOP INSIDE PANEL. 6. TOP PENETRATION NOT APPROVED, USE SIDE OR BOTTOM OF PANEL. 7. INSTALL ADDRESS LABEL ON SERVICE. 8. USE 1/4" BOLTS TO SUPPORT RISER CONDUIT. |