Permit: T06EL01851

Parcel: 11107090A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
MADE SEVERAL ATTEMPTS TO CALL PHONE NUMBER
NO ANSWER
LOCKED NO ACCESS
12/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. WIRING NOT COMPLETE
2. SMOKE DETECTORS NOT WORKING
3. NEED ARC FAULT PROTECTION FOR BEDROOMS - NEC 210.12
4. ROMEX CONNECTORS FOR BOXES, IDENTIFY NEUTRALS, GROUND BOXES AND FINISH ALL PREVIOUS CORRECTIONS -- WILL CHARGE REFEE IF NOT COMPLETE NEXT INSPECTION.
12/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
DO NOT CALL BEFORE COMPLETE
12/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/26/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. GROUNDING ELECTRODE CONDUCTOR/BONDING CONDUCTOR TO BE BURIED MIN. 12" OR SECURE TO STRUCTURE -- NEC 250.64
2. BOND CLAMP FOR GAS PIPE NOT LISTED FOR EARTH CONTACT -- NEC 110.3
3. BOND EXPOSED METAL DRAIN PIPE -- NEC 250.104
4. REMOVE PAINT UNDER BOND CLAMPS -- NEC 250.12
5. IF SUB-PANEL HAS METAL RACEWAY ALL THE WAY THEN NEUTRAL MUST "FLOAT" AND RACEWAY TO GROUND SUB-PANEL -- NEC 250.142 -- PROVIDE INTERIOR ACCESS.
6. NEED JOINT COMPOUND ON ALL ALUMINUM TERMINATION -- NEC 110
7. DRY NEUTRAL TO BE PROPERLY IDENTIFIED -- NEC 200.6