Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* MADE SEVERAL ATTEMPTS TO CALL PHONE NUMBER NO ANSWER LOCKED NO ACCESS |
|
| 12/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. WIRING NOT COMPLETE 2. SMOKE DETECTORS NOT WORKING 3. NEED ARC FAULT PROTECTION FOR BEDROOMS - NEC 210.12 4. ROMEX CONNECTORS FOR BOXES, IDENTIFY NEUTRALS, GROUND BOXES AND FINISH ALL PREVIOUS CORRECTIONS -- WILL CHARGE REFEE IF NOT COMPLETE NEXT INSPECTION. |
|
| 12/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DO NOT CALL BEFORE COMPLETE |
|
| 12/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 09/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. GROUNDING ELECTRODE CONDUCTOR/BONDING CONDUCTOR TO BE BURIED MIN. 12" OR SECURE TO STRUCTURE -- NEC 250.64 2. BOND CLAMP FOR GAS PIPE NOT LISTED FOR EARTH CONTACT -- NEC 110.3 3. BOND EXPOSED METAL DRAIN PIPE -- NEC 250.104 4. REMOVE PAINT UNDER BOND CLAMPS -- NEC 250.12 5. IF SUB-PANEL HAS METAL RACEWAY ALL THE WAY THEN NEUTRAL MUST "FLOAT" AND RACEWAY TO GROUND SUB-PANEL -- NEC 250.142 -- PROVIDE INTERIOR ACCESS. 6. NEED JOINT COMPOUND ON ALL ALUMINUM TERMINATION -- NEC 110 7. DRY NEUTRAL TO BE PROPERLY IDENTIFIED -- NEC 200.6 |