Inspection History Details
Permit: T06EL01848
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :$ CORRECTIONS APPROVED REINSPECTION FEE STILL NEEDS TO BE PAID PRIOR TO FINAL APPROVAL. |
|
| 12/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STILL HAVE A BRANCH CKT NOT IDENTIFIED ON TRANSFER SWITCH PANEL DIRECTORY -- NEC 408.4 2. WILL NEED TO PAY A REINSPECTION FEE. BEFORE FINAL APPROVAL. |
|
| 12/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. REMOVE OLD SERVICE AND FEEDER RACEWAY 2. BACKFILL ALL TRENCHES 3. IDENTIFY CKT'S ON THE PANEL DIRECTORY OF TRANSFER SWITCH. |
|
| 11/22/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHEET METAL SCREW NOT ALLOWED FOR BOND CONNECTION IN METER SECTION. 2. TIGHTEN ALL CONNECTIONS. 3. TIGHTEN MAIN BONDING SCREW 4. IDENTIFY "SERVICE DISCONNECT" 5. CONNECTIONS TO GROUND RING NOT INSPECTED |