Permit: T06EL01848


Addresses:

2451 N FAIRVIEW AV

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/18/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :$
CORRECTIONS APPROVED
REINSPECTION FEE STILL NEEDS TO BE PAID PRIOR TO FINAL APPROVAL.
12/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STILL HAVE A BRANCH CKT NOT IDENTIFIED ON TRANSFER SWITCH PANEL DIRECTORY -- NEC 408.4
2. WILL NEED TO PAY A REINSPECTION FEE. BEFORE FINAL APPROVAL.
12/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. REMOVE OLD SERVICE AND FEEDER RACEWAY
2. BACKFILL ALL TRENCHES
3. IDENTIFY CKT'S ON THE PANEL DIRECTORY OF TRANSFER SWITCH.
11/22/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/16/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHEET METAL SCREW NOT ALLOWED FOR BOND CONNECTION IN METER SECTION.
2. TIGHTEN ALL CONNECTIONS.
3. TIGHTEN MAIN BONDING SCREW
4. IDENTIFY "SERVICE DISCONNECT"
5. CONNECTIONS TO GROUND RING NOT INSPECTED